Error Messages During Teach-In Procedure - Intec MLC 8000 Operating Manual

Lift controller
Table of Contents

Advertisement

INTEC GmbH
Lift controller MLC 8000
22/12/2016
Operating manual V2.0

4.15 Error messages during teach-in procedure

Error: Lift did
not go to top
floor!
Door error
Lift not in
bottom floor
Teach in not
possible, check
lift state!
Time exceeded
State changed.
New state:
Xxxx
Floorcount error
Check SGM
VO switched
in doorzone
VU switched
in doorzone
SGE switched
in doorzone
Error on SGO
Error on SGU
Position of SGO
wrong!
Position of SGU
wrong!
Count direction
wrong!
Setup position
switch not done!
Encoder is not
counting
Encoder error
Door zone too
small for stop
distances!
Check settings!
During teach-in the lift could not reach the top floor.
Possible causes:
- Faulty door zone switch SGM or switching points for SGM set
incorrectl
- Lower prelimit switch VU has not switched off
- Upper prelimit switch VO has not switched on
Door closing error when starting the teach-in trip
Lift not located on the bottom floor when starting teach-in procedure.
The shaft switches must have the following states when starting
teach-in procedure (complete calibration or calibration shaft switches):
- door zone switch SGM switched on
- upper prelimit switch VO switched off and lower prelimit switch VU
switched on (if available) or reference switch SGE off (if available)
- SGO and SGU (if available) switched on
Tech-in not possible because actual lift state is not "Setup" (e.g.
Inspection, Emergency recall operation, error state).
Exceeded time between 2 status changes of SGM, SGO or SGU
during teach-in (see parameters "triptime[s]").
Lift state changed during teach-in (e.g. error state or emergency recall
operation switched on)
The door zone switch SGM has switched too often during the teach-in
procedure (e.g. due to bouncing of the switch).
Upper prelimit switch VO switched while the lift was inside the door
zone. Check switching point.
Lower prelimit switch VU switched while the lift was inside the door
zone. Check switching point.
Reference switch SGE switched while the lift was inside the door
zone. Check switching point.
Upper door zone switch SGO not working during teach-in.
Lower door zone switch SGU not working during teach-in.
Error in switching sequence SGO (SGO switched at undefined or at
wrong position). Possibly SGO and SGU are reversed.
Error in switching sequence SGU (SGU switched at undefined or at
wrong position). Possibly SGO and SGU are reversed.
Counting direction of the position encoder incorrectly. The two
channels of the encoder must be changed.
The teach-in of the braking distance was started before teach-in of the
floor positions (magnetic switches) was finished.
No signals from encoder during teach-in trip.
Check encoder and wiring!
Irregular encoder signals during teach-in trip. Check encoder and
wiring!
In normal case, the door zone (SGM or parameter "Vane length" if
using absolute encoder) should be adjusted so that the point where all
spped signals will be switched off is located inside door zone. The