INTEC GmbH
Lift controller MLC 8000
22/12/2016
Operating manual V2.0
Nr.
Error message
52/4
Final lim.insp.
52/4
Drive error-SL
52/5
Safety beam
52/16
SL bypass monit.
52/17
SL gear off
52/18
SL shaftdoor on
52/19
SL doortest err.
Description
paramet.")
Since the limit switch will be
monitored generally only
through the safety circuit
(normally no additional
separate contacts) the cause
of failure can also be at a
different contact within the
primary safety circuit.
Safety circuit inspection limit
switch open.
Error message from the drive
during a trip. At the same time,
the safety circuit was opened.
Since the drive usually also
detects an opened safety
circuit (drop off running
contactors), it is not sure if the
actual cause of the error is in
the drive or the safety circuit.
Safety light curtain is
interrupted during a trip.
According to EN81-20 it is
allowed to bypass safety circuit
of doors by a switch for service
purposes.
This switch must be monitored
by one or more feedback
inputs.
The error occurs if not all
monitoring inputs have the
same state.
Safety gear triggered (safety
gear contact opened)
Safety circuit shaft doors still
closed while doors are opened.
Fehler beim Test
Sicherheitskreis Schachttüren
90/196
Lift controller reaction
Emergency stop; start in opposite
direction possible
Emergency stop.
Back to normal operation if safety
line is closed and error message
from drive is off.
Emergency stop.
Safety beam will be resetted by
pressing a new car call or the reset
button of the safety beam.
Only emergency operation and
inspection active.
Error is only cleared if all
monitoring inputs are set if bypass
switch is activated.
For monitoring an additional input
"Safety line" - "Before gear" is
necessary.
Clearing this error is only possible
by an reset input ("Safety line" -
"Gear reset")
Test according to EN81-20.
Check safety circuit, check for
bypass wire.
Back to normal mode by switching
on inspection or recall operation for
at least 5s or by resetting the lift
controller.
Check wiring: If doors are
completely opened the safety unit