Intec MLC 8000 Operating Manual page 104

Lift controller
Table of Contents

Advertisement

INTEC GmbH
Lift controller MLC 8000
22/12/2016
Operating manual V2.0
Nr.
Error message
176/112 OP device err.
176/113 OP device ramp
176/114 OP dev. not out
176/115 OP dev. not in
176/116 OP dev. ramp on
176/117 OP dev. ramp off
176/128 Uncontr.movement
176/129 Input unc.move
176/131 No deceleration
176/132 Dec.circ.not off
176/144 LIMAX Floortab
176/145 LIMAX Insp.sig
176/146 LIMAX Relay test
192/1
Trip time out
192/2
LS or callmisuse
Description
error or after inspection trip).
Faulty condition of the OP
device (e.g. set both limit
switches)
OP-device is unlocked while
the lift wants to start
OP device can't move out
OP device can't move in
Ramp of OP device can't move
out
Ramp of OP device can't move
in
Lift moved out of the door zone
while the doors are open
(see EN81 Annex A3)
Lift controller has recognized
uncontrolled movement, but the
input to check the uncontrolled
movement state has not
switched on.
Lifts with slow down control
circuit: Lift didn't slow down to
defined speed at the final floors
Lifts with slow down control
circuit: Control circuit still
triggered at standstill
If using LIMAX Safe as
positioning system: Position
difference between LIMAX
Safe and HSE
If using LIMAX Safe as
positioning system: Inspection
signal inputs of LIMAX Safe
wrong
If using LIMAX Safe as
positioning system: The cyclic
relay test takes unusually too
long
Time between 2 state changes
of shaft switches SGM (door
zone) exceeded (Trip time
monitoring according to EN81;
parameter "Triptime[s]").
Number of trips on car calls, in
which the light screen has not
been interrupted, exceeded
104/196
Lift controller reaction
Back to normal operation if OP
device has defined state again.
See above
See above
See above
See above
See above
Out of operation.
Back to normal operation only by
operationg a special Reset switch
or by switching on emergency
recall operation.
Out of operation.
Back to normal operation only by
operationg a special Reset switch
or by switching on emergency
recall operation.
Emergency stop
Back to normal operation after a
few seconds.
Back to normal operation if control
circuit has right state again
Emergency stop
New setup procedure necessary
Check wiring of LIMAX Safe
Check LIMAX Safe; if this occurs
repeatedly,change LIMAX
Emergency stop, out of operation
All car calls cleared; no further
error reaction