Intec MLC 8000 Operating Manual page 19

Lift controller
Table of Contents

Advertisement

INTEC GmbH
Lift controller MLC 8000
22/12/2016
Operating manual V2.0
1. Menu level
2. Menu level
Timer parameter
3. Menu level
4. Menu level
Bot.limit
SL door test
Descr.
Manuf.
Year
Set.date
Traction
Nom.Ld.[kg]
Parktime[s]
Triptime[s]
Carlight[s]
Waitt.CC[s]
Waitt.LC[s]
Waitt.nC[s]
19/196
Description
position, it detects error "SL final limit"; otherwise at fault "SK
missing". This parameter is used for hydraulic lift, which has to stop
operation if the lift was at top final limit.
See above; position of bottom limit switch
If set to "Yes", according to EN81-20 the shaft door safety circuit is
checked after each trip (if the doors are completely openend).
For this the safety unit for door zone bypass is activated for a short
time and so power is switched to safety circuit input SL4.
At the same time safety circuit input SL3 must not have power,
otherwise the safety circuit shaft door is defective or bypassed. In this
case the lift controller goes out of operation and sets the error
message " SL shaftdoor on".
For these parameters, values or text may be entered for informative
purposes.
Thus, for example, better assignment can be done when the parameter
set is stored on the PC.
If the lift is not used for this time the lift will go to the specified parking
level.
(Note: as of version 1.32z these parameters aredisplayed in a separate
submenu "Special parameter" - "Parking trip")
Monitoring of travel movement according to EN81
Time to turn off the car light, when the lift parks with closed doors at a
floor
Time until door closing when the lift has approached a floor due to a
car call (not for main floor; see below)
Time until door closing when the lift has approached a floor due to a
landing call (whether simultaneously a car call existed).
(not for main floor; see below)
If the lift is on a floor and there is no further call, then the lift closes
after this time the doors after that time (unless "Parking with open
door" is set; see Door parameters)
(not for main floor; see below)