Intec MLC 8000 Operating Manual page 45

Lift controller
Table of Contents

Advertisement

INTEC GmbH
Lift controller MLC 8000
22/12/2016
Operating manual V2.0
1. Menu level
2. Menu level
3. Menu level
4. Menu level
Check ↑ [mm]
Check ↓ [mm]
Get apr.[mm]
Governor
Govern.[ms]
Holding bolts
Hold.bolts
Stop pos.[mm]
Stop min[mm]
Stop max [mm]
Hold.zone[mm]
Repeat hold.
Pump.del[ms]
Pump.off[mm]
Relays
45/196
Description
Position below the level position of top floor, where a folding apron
must be fully unfolded again
See above; setting for bottom floor
Position below bottom floor for getting an automatic folding apron.
If this setting is not equal 0, than the lift will always go down up to this
positionto get the folding apron, even if the feedback contact from
apron is already switched on.
When using the overspeed governor with additional magnetic coil for
protection against uncontrolled movement:
always: The coil on the over speed governor is only switched off in
case the shelter monitoring has been triggered.
moving: The coil on the over speed governor is switched on while the
lift is moving.
mov.+DZ: The coil on the over speed governor is switched on while
the lift is moving and while the lift stops inside the door zone
If a feedback contact exits on the over speed governor: Maximum
waiting time for feedback contact while switching on and off.
If no feedback contact exists: delay time after switching the output
"Governor" on or off.
Parameters for lifts with holding bolts
Specifies whether the lift is equipped with holding bolts (yes / no)
Specifies how many mm lift should stop when entering a floor above
this floor, so that the holding bolts can be pulled out or how many mm
the lift has to move up to bring in the holding bolts before starting a
new trip.
Minimum distance above a floor to pull in / pull out the holding bolts.
Maximum distance above a floor to pull in / pull out the holding bolts.
Area in mm where the lift could reached the holding position.
Indicates, if the lift should move down again if the lift is still in holding
zone (see above), but the signal "Holding reached" did switch off.
Delay time by hydraulic lifts to start hydraulic pump again, if low
pressure is detected whilem the lift is in holding position.
Position above the level position where the hydraulic re-pumping is
switched off again at the latest (see also parameter above). In the
normal case, the pump is, however, turned off when the pressure loss
is compensated.
Switching status of the holding bolts relays after the holding bolts are