Lift controller MLC 8000
22/12/2016
Operating manual V2.0
Main function
Sub function/
Direction/
Floor
Clock run 2
Clock run 3
Clock run 4
Clock run 5
Safety beam
Earthquake
Auto-call
- Up peak
- Dn peak
Final limit
Em.stop
Phase error
AWG2 err.
Insp.limit
Service mode
Insp.Reset
SL bypass
Floor
Doors
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Signal no.
-
-
-
Signal no.
Direction
-
-
-
-
-
Signal no.
-
125/196
Description
Input to start clock runs.
More settings see „Special param." – "Clock run" and also "Door releases"
See above
See above
See above
Safety beam for lift without car door
Earthquake sensor input (lift is switched off immediately)
Starting the autocall function
More parameter see „Special param." – "Auto-call funct."
Inputs for lifts with high traffic: During up peak (down peak) the lift only serves
landing calls in up direction (down direction) and ignores the landing calls in
opposite direction.
Note: This function may be activated by this input as well as with the internal
timer function (see "Group control")
Additional contact on final limit switch to check, if the final limit switch is
opened.
Emergency stop push operated (2 contact additional to contact in safety circuit)
With setting "Signal no." it is possible to connect different emergency stop
pushes (e.g. emergency stop pit, ememergency stop inspection, ...) to the lift
controller.
Note: The same signal no. should not exist more than 1 time in a lift.
Contact from phase relay
Error signal from AWG2 evaluation unit (POS2) if the "Double-AWG" is used for
positioning
By using the signal no. (1 and 2) the error signal may be connected twice for
safety reasons (the evaluation board POS2 has 2 error outputs - 1 standard and 1
inverted)
Input for inspection limit switch
In service mode only Inspection, Emergency recall operation and travel
commands from keypad may be used, otherwise lift is out of operation.
Reset button input to return back from inspection pit mode
Safety circuit car or shaft door shorted (according to EN81-20) - lift only moves
now with recall operation or inspection.