Intec MLC 8000 Operating Manual page 156

Lift controller
Table of Contents

Advertisement

INTEC GmbH
Lift controller MLC 8000
22/12/2016
Operating manual V2.0
Position
Function
JP1
Jumper CAN bus terminator CAN1 (control bus)
→ Jumper must be set if MCU is located at the end of the CAN bus cable (control bus).
JP2
Jumper CAN bus terminator CAN2 (shaft bus)
→ Jumper must be set if MCU is located at the end of the CAN bus cable (shaft bus).
JP3
Jumper CAN bus terminator RS485
→ Jumper must be set if MCU is located at the end of the RS485 bus cable.
JP4
Setting for encoder type connected to MCU:
JP5
- 5V-Encoder signals: Set both jumpers
- 24V (10...30V) Encoder signals: Remove both jumpers
JP6
Jumper for Software download (Boot mode). Remove jumper for normal operation.
BT1
Battery for real time clock MCU
R1
Potentiometer (variable resistor) for display contrast
S1
Reset button
S2
internal use only
U1
Parameter EEPROM for all lift parameters.
U2
Backup EEPROM, contains a backup copy of all parameters
D1
bis
D9
Status LED for state of relays KM1 to KM8 and alarm call relay KM-CA.
+5V
Status LED for 5V controller power supply
FAU
Fault LED (lift controller fault)
RUN
LED "Software is running"
MAI
Maintenance LED (Maintenance necessary)
XM1
RS-232 interface (mainly used for software update)
XM2
CA-IN
0V
0V
+FLU
MSI
XM3
0V
+CA
CA1
CA2
8CL
8OP
8CM
7CL
7OP
7CM
6CL
6OP
6CM
XM4
n.c.
Δ
Υ
UP
Alarm call input (low aktiv); directly connected to alarm relay KM-CA
0V – power supply
0V – power supply
Battery buffered 24V power supply with integrated series resistor (2kΩ) for
connecting an LED as flush signal
Input for door zone switch MSI
0V – power supply
Alarm call relay KM-CA, N.O. contact.
Other side of contact is connected internally with battery buffered 24V power
supply.
Mainly used for alarm horn.
Alarm call relay KM-CA, N.O. contact., potential-free
Relay KM8 (MCU Output 8): Output relay KM8, N.C. contact
Relay KM8 (MCU Output 8): Output relay KM8, N.O. contact
Relay KM8 (MCU Output 8): Output relay KM8, common
Relay KM7 (MCU Output 7): Output relay KM7, N.C. contact
Relay KM7 (MCU Output 7): Output relay KM7, N.O. contact
Relay KM7 (MCU Output 7): Output relay KM7, common
Relay KM6 (MCU Output 6): Output relay KM6, N.C. contact
Relay KM6 (MCU Output 6): Output relay KM6, N.O. contact
Relay KM6 (MCU Output 6): Output relay KM6, common
Not connected
Relay KM5 (MCU Output 5): N.O. contact; Default: Delta contactor (Hydraulic
lifts); Brake contactor (Rope lifts)
Relay KM5 (MCU Output 5): N.C. contact; Default: Star contactor (Hydraulic
lifts)
Relay KM4 (MCU Output 4): N.O. contact; Default: Upwards contactor