Intec MLC 8000 Operating Manual page 108

Lift controller
Table of Contents

Advertisement

INTEC GmbH
Lift controller MLC 8000
22/12/2016
Operating manual V2.0
Level zone too
small for lift
speed! Automatic
calculation <ET>
Re-level speed
Too fast for
Lift with UCM!
Teach-in not
neccessary, just
set param."Setup
ready" to Yes
teach-in trip has however measured that this is not the case in at least
1 floor. Therefore, either (if possible) change settings on the drive to
shorten stopping distance (lower arrival speed v0) or enlarge the door
zone.
If this is not possible the stopping accuracy may be not very good.
The level zone (parameters "Level zone ↑" and "Level zone ↓") is too
small in relation to the measured braking distances for relevel spped
vN. Thus, re-levelling is not possible.
When pressing ENTER the parameters for the flush zone are adjusted
automatically. However, it is better to lower the re-levelling speed vN
on the drive if possible.
For lifts with safety unit to protect against uncontrolled movement
UCM (EN81-A3) the lift must be switched off if the re-level speed
exceeds 200 mm/s. But the speed measurement during set-up
procedured measured a re-level speed higher than 200 mm/s.
Adjust re-level speed!
This message appears if it is not necessary to do a teach-in trip (e.g.
for lift with only magnetic switches for positioning).
108/196