Error message
128/xx
SMS send error
Fax send error
PC send error
CAN faulty
129/16
CAN HW Overrun
129/17
CAN SW Overrun
129/18
CANB HW Overrun
129/19
CANB SW Overrun
129/20
CAN fault RXC
129/21
CAN HW Overr.1
129/22
CAN HW Overr.2
129/23
CAN HW Overr.3
129/32
CAN fault Passiv
129/48
No connect xxx
(xxx = PCB name)
129/49
No HSE conn.
129/50
Mand.ESE fault
129/51
Mand.TSE fault
129/64
CAN bus off
Description
according to CANopen lift
DSP417: The drive parameters
do not correspond to the
parameters stored in the lift
controller.
Error while sending an SMS,
fax or PC alarm message.
Failure in the data transmission
on the CAN bus (CANB = shaft
bus).
If this error occurs, the last
CAN bus message is
automatically repeated, so that
there is no data loss.
This error can, for example,
occur on the CAN bus when
switching on the main switch or
when connecting new modules.
By increased number of such
errors check CAN bus
connection (see section
„Troubleshooting at CAN bus
faults").
No reception of the "Heartbeat"
message of a module (xxx) by
the HSE.
All CAN-Bus units send a
"Heartbeat" message within a
specified time for supervising.
No reception of the "Heartbeat"
message of the HSE.
Any ESE marked as
"mandatory" is not available
(defective or data transmission
fault).
Any TSE marked as
"mandatory" is not available
(defective or data transmission
fault).
Automatic shutdown of the
CAN bus due to many
93/196
Lift controller reaction
start menu item "Read from drive"
in menu "Drive parameter")
Check data transmission line and
receiver nummber / address.
Depending on the CAN Error type:
Automatic repeated transmission
of the disturbed CAN bus
message; no further error reaction.
Emergency stop.
If the "heartbeat" of this module is
received again, the system returns
to normal operation.
If this error occurs by a TSE or
ESE assembly, then there is no
emergency.
Emergency stop.
Following an internal diagnostic
and then return to normal
operation.
If ESE or TSE modules do not
receive heartbeat of HSE for more
than 5 seconds they will switch off
all outputs and switch on "Out of
order" outputs.
Finish last trip; then out of
operation
Finish last trip; then out of
operation
Emergenca stop, thereafter, an
internal test of the data transfer