Intec MLC 8000 Operating Manual page 56

Lift controller
Table of Contents

Advertisement

INTEC GmbH
Lift controller MLC 8000
22/12/2016
Operating manual V2.0
1. Menu level
2. Menu level
Maintenance
Group control
3. Menu level
4. Menu level
Drivedelay[s]
Door off[s]
Door delay[s]
Car disp[s]
Land.disp[s]
Traff.off[s]
Interval
Action
Warning
Doorclose[s]
Door-reopen
Door-block.
56/196
Description
Waiting time after returning the drive from the standby mode. At latest
after the end of that time the fault signal of the drive must report the
operational state.
f the lift stands with closed doors for this time in a floor, then the
doors can be shut down by the special output "Door Standby".
Waiting time for returning back from standby mode until door drive is
ready.
Time delay before switching off the level indicator inside the car when
the lift is not in use (for displays with CAN bus only)
Time delay before switching off the level indicator at the landings
when the lift is not in use (for displays with CAN bus only)
If the lift is in a floor level for this time period without any call then all
traffic lights for a car lift will be switched off.
Settings for monitoring maintenance intervals
If maintenance interval monitoring is enabled here the number of trips
until next necessary maintenance is set.
Setting this parameter to 0 this function is deactivated.
If monitoring is enabled the maintenance counter must be re-started
after each maintenance (see menu "Statistics" - "Maint.count"
Reaction at the end of the maintenance interval:
„Calls off": all calls disabled
„CC off" Landing calls enabled, but car calls off
„Display": the "Out of service" indicators are turned on, otherwise the
lift goes on as normal.
Number of trips before the maintenance counter is reached the lift sets
a warning.
Parameters for lift groups
If door closing is not possible inside this time the lift will inform the
other lifts in a group.
Depending on some other facts another lift may handle the landing
calls of this lift after that time.
Number of door reopenings (by light screen or door open push) after
that another lift will handle landing calls of this lift. This will prevent
from blocking thegroup function by this lift.
By setting this parameter to 0 this function is deactivated.
See above, but here is not the max. number of re-opening of the door
monitored, but the time duration in which the door can not be closed
(e.g. door-open-button permanently activated or light screen
constantly interrupted).