Intec MLC 8000 Operating Manual page 18

Lift controller
Table of Contents

Advertisement

INTEC GmbH
Lift controller MLC 8000
22/12/2016
Operating manual V2.0
1. Menu level
2. Menu level
3. Menu level
4. Menu level
Vane length
Cl.calls[mm]
Level zone ↑
Level zone ↓
Incr./m
v nominal
v relevel
v brake
Top limit
18/196
Description
- reopen: re-opens the door if new landing call is pressed
- ignore: if the lift already starts door closing while the new landing
call was presses the lift controller will continue closing the door and
handle this call later
- other lift (only for group of lifts): If a new landing call is pressed
another lift of the group will go to this floor even if there is alrady a lift
with open doors located in this floor
Length of the door zone (area where the door zone switch SGM is
turned on)
Only if this parameter is entered correctly, the control values can
specify in mm or mm/s (the lift controller calculates the relation
between resolution of incremental encoder and "real length in mm)
If the vane length is not identical in all floors, the vane langth on the
2nd floor length must be entered here.
Distance in mm from the target floor, in which the calls for this floor
will be cleared (lamp off). When set to "0", the calls are cleared in the
moment the lift starts slowing down
(Note: Clearing a call before the lift slows down is not possible.)
Position in mm above floor level where the lift starts re-levelling (only
if parameter "Relevelling" is set to "yes")
Note:
When positioning via the motor encoder and magnetic
switches the leveling zone is formed by the switch SGO / SGU. This
parameter is of no significance in this case.
See above; position below floor level
Resolution of position encoder related to travel distance in mm.
This parameter is automatic calculated during set-up trip (setting of
parameter "Vane length" - see above - must be correct!)
If the lift has only 2 floors this parameter must be calculated and set
manually.
Rated speed ( for speed monitoring)
Relevelling speed ( for speed monitoring)
For manual evacuation through brake opening via UPS in case of
power failure (machine room-less lifts): Upon reaching this speed the
control allows the mechanical brake to come up again ("interval
braking" for speed limit)
Distance of the upper final limit switch above top floor. This parameter
is used exclusively for the detection of errors if the lift is on the top
floor and the primary safety circuit (SL1) fails. If the lift is above this