Intec MLC 8000 Operating Manual page 105

Lift controller
Table of Contents

Advertisement

INTEC GmbH
Lift controller MLC 8000
22/12/2016
Operating manual V2.0
Nr.
Error message
192/3
Alarm call
193/4
Trip time stop
241/1
Door x close err.
242/1
243/1
241/2
Door x open error
242/2
243/2
241/3
Door x reop.error
242/3
243/3
241/4
Door x opn.switch
242/4
243/4
241/5
Door x cls.switch
242/5
243/5
241/6
SL Door x shorted
242/6
243/6
241/7
Door x nudging
Description
(parameter „Check LS").
Possible reason:
- car call misuse by pressing all
car call buttons
- Light screen not working
Emergency call button was
pressed.
The emergency call is only
displayed in the fault memory,
if an input of HSE (normally
input 14, since it is already
connected to the HSE with the
emergency line) has been
parameterized as "Alarm call".
Trip time exceeded even
though the lift is already on
braking / stopping
Timeout while door is closing
Timeout while door is opening
Timeout while door is closing
after reopening by light screen
Dooropen-limit-switch of a door
is suddenly deactivated without
door command.
Doorclose-limit-switch of a door
is suddenly deactivated without
door command.
Safety circuit of car door
shorted
If the door has no limit switches
the reason for this error may be
a defective door controller /
door motor
Forced door closing initiated by If possible, lift closes the door with
105/196
Lift controller reaction
No further error reaction
Emergency stop
Back to normal operation after 2
sec.
Check door motor / door controller
Check setting of parameter
"Closetime [s]"
Lift controller starts closing several
times (parameter "Close attemps"),
than all calls are cleared.
New close attemps if new call is
pressed.
Check door motor / door controller
Check setting of parameter
"Opentime [s]"
Lift controller starts opening
several times (parameter "Open
attemps"), than all calls are cleared
and lift out of operation.
New open attemps if new call is
pressed.
See above
Lift controller retries to open / close
the doors by a new call
Lift controller retries to open / close
the doors by a new call
Out of operation (dangerous state).
Check safety switch and wiring