Explanation Of Status Word Bit - Danfoss iC2 Application Manual

Micro frequency converters
Table of Contents

Advertisement

Application Guide | iC2-Micro Frequency Converters
Follower-master
STW
Bit
no.:
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Figure 66: Status Word
Table 56: Status Word According to FC Profile
Bit
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15

Explanation of Status Word Bit

6.1.8.4
Bit 00, Control Not Ready/Ready
Bit 00=0: The drive trips.
Bit 00=1: The drive controls are ready but the power component does not necessarily receive any supply (if there is 24 V external supply
to controls).
Bit 01, Drive Ready
Bit 01=0: The drive is not ready.
Bit 01=1: The drive is ready for operation, but the coasting command is active via the digital inputs or via serial communication.
Bit 02, Coast Stop
Bit 02=0: The drive releases the motor.
100
| Danfoss A/S © 2024.03
Output freq.
Bit = 0
Control not ready
Drive not ready
Coasting
No error
No error
Reserved
No error
No warning
Speed≠reference
Local operation
Out of frequency limit
No operation
Drive OK
Voltage OK
Torque OK
Timer OK
Bit = 1
Control ready
Drive ready
Enable
Trip
Error (no trip)
Triplock
Warning
Speed=reference
Bus control
Frequency limit OK
In operation
Stopped, auto start
Voltage exceeded
Torque exceeded
Timer exceeded
AB413939445838en-000301 / 130R1254