Application Guide | iC2-Micro Frequency Converters
Data type:
uint16
P 2.3.10 Fast Mains Phase Loss Min. Power
Fast detection is not activated if the actual power is lower than the value specified in the parameter.
Default value:
10
Parameter
1418
number:
Data type:
uint16
P 2.3.13 Auto DC Braking
Protective function against overvoltage at coast in IT grid environment. This parameter is active only when [1] On is selected in this
parameter, and IT grid options are selected in P 1.2.2 Grid Type.
Default value:
1 [On]
Parameter
7
number:
Data type:
enum
The following are the selections for the parameter.
Selection number
Selection name
0
Off
1
On
P 2.3.14 Max Output Frequency
Enter the maximum output frequency value. P 2.3.14 Max Output Frequency specifies the absolute limit on the frequency converter
output frequency for improved safety in applications where accidental over-speeding must be avoided. This absolute limit applies to all
configurations and is independent of the setting in P 5.4.2 Configuration Mode.
Default value:
Size Related
Parameter
419
number:
Data type:
uint16
The parameter cannot be adjusted while the motor is running. Maximum output frequency cannot exceed 10% of the inverter
switching frequency in P 2.4.3 Switching Frequency.
P 2.3.15 Action at Inverter Fault
Select how the frequency converter reacts when an overvoltage, overcurrent, short circuit, or grounding fault occurs.
Default value:
1 [Warning]
114
| Danfoss A/S © 2024.03
Access type:
Parameter type:
Unit:
Access type:
Parameter type:
Unit:
Access type:
Selection description
The function is not active.
The function is active.
Parameter type:
Unit:
Access type:
  NOTICE
Parameter type:
Read/Write
Range (0–100)
%
Read/Write
Selection
Read/Write
Range (0–500)
Hz
Read/Write
Selection
AB413939445838en-000301 / 130R1254