Danfoss iC2 Application Manual page 166

Micro frequency converters
Table of Contents

Advertisement

Application Guide | iC2-Micro Frequency Converters
Selection number
Selection name
0
Disabled
1
Enabled
2
Enabled Always
3
Enabled Reference Direction
4
Enabled Always Reference Direction
P 5.6.4 Start Speed [Hz]
Use this parameter to set the motor start speed. After the start signal the output speed leaps to the set value. This parameter can be used
for vertical movement applications (such as cone rotor). Set the start function in P 5.6.2 Start Function to [3] Start Speed Clockwise, [4]
Horizontal Operation, or [5] VVC+ Clockwise, and set a start delay time in P 5.6.1 Start Zero Speed Time.
Default value:
Size Related
Parameter
175
number:
Data type:
uint16
P 5.6.5 Start Current
Use this parameter to set the boost current for the motor. Some motors, for example cone-rotor motors, need extra current or starting
speed to disengage the rotor. To obtain this boost, set the required current in P 5.6.5 Start Current. Set the start speed with P 5.6.4 Start
Speed [Hz]. Set parameter P 5.6.2 Start Function to [3] Start Speed Clockwise or [4] Horizontal Operation, and set a start delay time in P
5.6.1 Start Zero Speed Time.
Default value:
Size Related
Parameter
176
number:
Data type:
uint32
P 5.6.6 Breakaway Current Boost
Use this parameter to set the breakaway current boost. The frequency converter provides higher current than normal current levels to
enhance breakaway-torque capacity.
Default value:
0 [Off]
Parameter
422
number:
Data type:
enum
The following are the selections for the parameter.
166
| Danfoss A/S © 2024.03
Selection description
No function.
Enable the frequency converter to catch and control a spinning
motor. When P 5.6.3 Enable Flying Start is enabled, P 5.6.1 Start
Zero Speed Time, and P 5.6.2 Start Function have no function.
Enable flying start at every start command.
Enable the frequency converter to catch and control a spinning
motor. The search is performed only in the reference direction.
Enable flying start at every start command. The search is
performed only in the reference direction.
Parameter type:
Unit:
Access type:
Parameter type:
Unit:
Access type:
Parameter type:
Unit:
Access type:
Range (0.0–500.0)
Hz
Read/Write
Range (0.00–1000.00)
A
Read/Write
Selection
Read/Write
AB413939445838en-000301 / 130R1254