Application Guide | iC2-Micro Frequency Converters
Selection number
Selection name
4
Motor Current
6
Motor power
7
Motor voltage
12
Analog input AI33
13
Analog input AI34
19
Pulse input FI18
20
Alarm number
30
Counter A
31
Counter B
P 8.4.3.2 Comparator Operator
Select the operator to be used in the comparison. This is an array parameter containing comparator operators 0–5.
Default value:
0
Parameter
1311
number:
Data type:
enum
The following are the selections for the parameter.
Selection number
Selection name
0
Less Than (<)
1
Approx. Equal (~)
2
Greater Than (>)
P 8.4.3.3 Comparator Value
Enter the "trigger level" for the variable which is monitored by this comparator. This is an array parameter containing comparator values
0–5.
Default value:
0
Parameter
1312
number:
Data type:
int32
206
| Danfoss A/S © 2024.03
Selection description
Motor current in [A].
Motor power in either [kW] or [hp].
Motor voltage in [V].
Expressed as actual value.
Expressed as actual value.
Expressed as actual value.
Shows number of the alarm.
Number of counts.
Number of counts.
Parameter type:
Unit:
Access type:
Selection description
Result of evaluation is True if variable selected in P 8.4.3.1
Comparator Operand is smaller than fixed value in P 8.4.3.3
Comparator Value. Result is False if variable selected in P 8.4.3.1
Comparator Operand is greater than fixed value in P 8.4.3.3
Comparator Value.
Result of evaluation is True if variable selected in P 8.4.3.1
Comparator Operand is approximately equal to fixed value in P
8.4.3.3 Comparator Value.
Inverse logic of selection 0.
Parameter type:
Unit:
Access type:
Selection
Read/Write
Range (-9999000–9999000)
Read/Write
AB413939445838en-000301 / 130R1254