Danfoss iC2 Application Manual page 153

Micro frequency converters
Table of Contents

Advertisement

Application Guide | iC2-Micro Frequency Converters
This parameter is active only when P 5.5.1.1 Control Place Selection is set to [0] Digital and control word.
Default value:
3 [Logic OR]
Parameter
851
number:
Data type:
enum
The following are the selections for the parameter.
Selection number
Selection name
0
Digital input
1
Bus
2
Logic AND
3
Logic OR
P 5.5.2.3 DC Brake Select
Use this parameter to select whether the DC brake is controlled via the terminals (digital input) and/or via the fieldbus.
This parameter is active only when P 5.5.1.1 Control Place Selection is set to [0] Digital and control word.
Default value:
3 [Logic OR]
Parameter
852
number:
Data type:
enum
The following are the selections for the parameter.
Selection number
Selection name
0
Digital input
1
Bus
2
Logic AND
3
Logic OR
P 5.5.2.4 Start Select
Danfoss A/S © 2024.03
  NOTICE
Parameter type:
Unit:
Access type:
Selection description
Activate the quick stop command via a digital input.
Activate the quick stop command via the serial communication
port or fieldbus option.
Activate the quick stop command via the fieldbus/serial
communication port and also via 1 of the digital inputs.
Activate the quick stop command via the fieldbus/serial
communication port or via 1 of the digital inputs.
  NOTICE
Parameter type:
Unit:
Access type:
Selection description
Activate the DC brake command via a digital input.
Activate the DC brake command via the serial communication
port or fieldbus option.
Activate the DC brake command via the fieldbus/serial
communication port and additionally via 1 of the digital inputs.
Activate the DC brake command via the fieldbus/serial
communication port or via 1 of the digital inputs.
Selection
Read/Write
Selection
Read/Write
AB413939445838en-000301 / 130R1254 |
153