Application Guide | iC2-Micro Frequency Converters
Set the reference value to correspond to the minimum position of the control panel potentiometer.
Default value:
0.000
Parameter
681
Number
Data type:
int32
Live Zero (Menu Index 9.5.6)
7.9.3.5
P 9.5.6.1 Live Zero Response
Enter the timeout time. The function set in P 9.5.6.2 Live Zero Timeout Function is activated when the input signal on terminal is below
50% of the minimal value (for example, the minimal value for Terminal 33 voltage mode is P 9.5.2.3 T33 Low Voltage) for a time period
defined in the parameter.
Default value:
10
Parameter
600
Number
Data type:
uint8
P 9.5.6.2 Live Zero Timeout Function
Select the timeout function. The function set in the parameter is activated when the input signal on terminal is below 50% of the
minimal value (for example, the minimal value for Terminal 33 voltage mode is P 9.5.2.3 T33 Low Voltage) for a time period defined in P
9.5.6.1 Live Zero Response.
Default value:
0 [Off]
Parameter
601
Number
Data type:
enum
The following are the selections for the parameter.
Selection number
0
1
2
3
4
5
256
| Danfoss A/S © 2024.03
Parameter type:
Unit:
Access type:
Parameter type:
Unit:
Access type:
Parameter type
Unit:
Access type:
Selection name
Off
Freeze Output
Stop
Jogging
Max Speed
Stop and Trip
Range (-4999.000–4999.000)
–
Read/Write
Range (1–99)
s
Read/Write
Selection
–
Read/Write
AB413939445838en-000301 / 130R1254
Need help?
Do you have a question about the iC2 and is the answer not in the manual?
Questions and answers
Multi inputs control motor speeds setting Example, 1Float is on level means motor off 2nd number float on means motor 25 hz running 3rd number float on means motor 50hz running This format control settings needed