The PKE Field
6.1.6.2.7
The PKE field contains 2 subfields:
Parameter command and response (AK)
l
Parameter number (PNU)
l
PKE
AK
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Figure 60: PKE Field
Bits 12–15 transfer parameter commands from master to follower and return processed follower responses to the master.
Table 25: Parameter Commands
Parameter commands master->follower
Bit number
15
14
13
0
0
0
0
0
0
0
0
1
0
0
1
1
1
0
1
1
1
1
1
1
Table 26: Response
Response follower->master
Bit number
15
14
13
0
0
0
0
0
0
0
0
1
Danfoss A/S © 2024.03
IND
PWE
PWE
high
low
PNU
Parameter command
12
0
No command.
1
Read parameter value.
0
Write parameter value in RAM (word).
1
Write parameter value in RAM (double word).
1
Write parameter value in RAM and EEPROM (double word).
0
Write parameter value in RAM and EEPROM (word).
1
Read text.
Response
12
0
No response.
1
Parameter value transferred (word).
0
Parameter value transferred (double word).
AB413939445838en-000301 / 130R1254 |
79