Application Guide | iC2-Micro Frequency Converters
In automatic reset mode, the motor can start without a warning.
The following are the selections for the parameter.
Selection number
Selection name
0
Manual reset
1
Automatic reset x 1
2
Automatic reset x 2
3
Automatic reset x 3
4
Automatic reset x 4
5
Automatic reset x 5
6
Automatic reset x 6
7
Automatic reset x 7
8
Automatic reset x 8
9
Automatic reset x 9
10
Automatic reset x 10
11
Automatic reset x 15
12
Automatic reset x 20
13
Infinite auto reset
14
Reset at power-up
If the specified number of automatic resets is reached within 10 minutes, the frequency converter enters [0] Manual Reset Mode.
After the manual rest is performed, the setting of P 6.6.6 Reset Mode reverts to the original selection. If the number of automatic
resets is not reached within 10 minutes, or when a manual reset is performed, the internal automatic reset counter returns to 0.
P 6.6.7 Automatic Restart Time
Use this parameter to enter the time interval from the trip event to the automatic reset. This parameter is active when P 6.6.6 Reset Mode
is set to a selection between [1]–[13].
Default value:
10
Parameter
1421
number:
Data type:
uint16
A value of 0s cannot be set when P 6.6.6 Reset Mode is set to [13] Infinite auto reset.
194
| Danfoss A/S © 2024.03
  NOTICE
Selection description
Perform a reset via Stop/Reset button or via the digital inputs.
Select for continuous resetting after tripping.
  NOTICE
Parameter type:
Unit:
Access type:
  NOTICE
Range (0–600)
s
Read/Write
AB413939445838en-000301 / 130R1254