Application Guide | iC2-Micro Frequency Converters
Connectivity (Menu Index 10)
7.10
FC Port Settings (Menu Index 10.1)
7.10.1
P 10.1.1 Protocol
Select the protocol for the integrated RS485 port.
Default value:
0 [FC]
Parameter
830
number:
Data type:
enum
The following are the selections for the parameter.
Selection number
Selection name
0
FC
2
Modbus RTU
P 10.1.2 Address
Enter the address for the RS485 port. Valid range: 1-126 for FC-bus or 1-247 for Modbus.
Default value:
1
Parameter
831
number:
Data type:
uint8
P 10.1.3 Baud Rate
Select the baud rate for the RS485 port..
Default value:
2 [9600]
Parameter
832
number:
Data type:
enum
The following are the selections for the parameter.
Selection number
0
1
2
3
4
Danfoss A/S © 2024.03
Parameter type:
Unit:
Access type:
Selection description
Communication according to the FC protocol.
Communication according to the Modbus RTU protocol.
Parameter type:
Unit:
Access type:
Parameter type:
Unit:
Access type:
Selection name
2400 Baud
4800 Baud
9600 Baud
19200 Baud
38400 Baud
AB413939445838en-000301 / 130R1254 |
Selection
–
Read/Write
(0–247)
–
Read/Write
Selection
–
Read/Write
257