Application Guide | iC2-Micro Frequency Converters
Parameter
713
number:
Data type:
uint16
P 5.10.6 Trip Delay at Torque Limit
Use this parameter to define the delay for tripping the torque warning. When the output torque reaches the torque limit, a warning is
triggered. If the torque limit warning is continuously present for the period specified in this parameter, the frequency converter trips. To
disable the feature, enter the value of 60 s.
Default value:
60
Parameter
1425
number:
Data type:
uint8
Mechanical Brake Control (Menu Index 5.11)
7.6.10
P 5.11.1 Brake Closing Speed
Use this parameter to set the motor frequency when the mechanical brake activates, when a stop condition is present.
Default value:
0.0
Parameter
222
number:
Data type:
uint16
P 5.11.2 Brake Close Time
Use this parameter to enter the brake delay time for the coast after ramp-down time. The shaft is held at zero speed with full holding
torque. Ensure that the mechanical brake has locked the load before the motor enters coast mode.
Default value:
0.0
Parameter
223
number:
Data type:
uint8
P 5.11.3 Release Brake Current
Use this parameter to set the motor current for release of the mechanical brake, when a start condition is present. The upper limit is
specified with P 2.1.5 Inv. Max. Current.
Default value:
0.00
Parameter
220
number:
Data type:
uint32
176
| Danfoss A/S © 2024.03
Unit:
Access type:
Parameter type:
Unit:
Access type:
Parameter type:
Unit:
Access type:
Parameter type:
Unit:
Access type:
Parameter type:
Unit:
Access type:
s
Read/Write
Range (0–60)
s
Read/Write
Range (0.0–400.0)
Hz
Read/Write
Range (0.0–5.0)
s
Read/Write
Range (0.00–100.00)
A
Read/Write
AB413939445838en-000301 / 130R1254