Application Guide | iC2-Micro Frequency Converters
Parameter
152
number:
Data type:
uint16
P 4.4.4.13 VT Level
Enter the level of motor magnetization at low speed. Selecting a low value reduces energy loss in the motor but also reduces load
capability.
Default value:
66
Parameter
1440
number:
Data type:
uint8
This parameter is not active when P 4.2.1.1 Motor Type is set to options that enable PM motor mode.
P 4.4.4.14 Min. Current at Low Speed
Enter the minimum motor current at low speed. Increasing this current improves motor torque at low speed. The parameter is only
enabled for PM motors.
Default value:
Size Related
Parameter
166
number:
Data type:
uint32
Dead Time Compensation (Menu Index 4.4.4.5)
7.5.3.5
P 4.4.5.1 Dead Time Compensation Level
Level of applied dead time compensation in percentage. A high level (>90%) optimizes the dynamic motor response, a level from 50–
90% good for both motor-torque ripple minimization and the motor dynamics, a zero level turns off the dead time compensation.
Default value:
Size Related
Parameter
1407
number:
Data type:
uint8
P 4.4.5.2 Dead Time Bias Current Level
Set a bias signal (in [%]) to add to the current-sense signal for dead time compensation.
Default value:
Size Related
Parameter
1409
number:
Data type:
uint8
Danfoss A/S © 2024.03
Unit:
Access type:
Parameter type:
Unit:
Access type:
NOTICE
Parameter type:
Unit:
Access type:
Parameter type:
Unit:
Access type:
Parameter type:
Unit:
Access type:
Hz
Read/Write
Range (40–90)
%
Read/Write
Range (Size Related)
%
Read/Write
Range (0–100)
–
Read/Write
Range (0–100)
%
Read/Write
AB413939445838en-000301 / 130R1254 |
135
Need help?
Do you have a question about the iC2 and is the answer not in the manual?