Application Guide | iC2-Micro Frequency Converters
Use this parameter to select the ramp type, depending on requirements for acceleration and deceleration. A linear ramp provides
constant acceleration during ramping. Sine Ramp and Sine 2 Ramp provide non-linear acceleration.
Default value:
0 [Linear]
Parameter
340
number:
Data type:
enum
The following are the selections for the parameter.
Selection number
Selection name
0
Linear
1
Sine Ramp
2
Sine 2 Ramp
P 5.5.4.2 Ramp 1 Accel. Time
Use this parameter to enter acceleration time. The values range from 0 Hz to the motor frequency defined in P 4.2.2.4 Nominal
Frequency. Select a ramp up time such that the output current does not exceed the current limit in P 2.7.1 Output Current Limit % during
ramping.
Default value:
Size Related
Parameter
341
number:
Data type:
uint32
P 5.5.4.3 Ramp 1 Decel. Time
Use this parameter to enter the deceleration time. The values range from the motor frequency defined in P 4.2.2.4 Nominal Frequency to
0 Hz. Select a ramp down time such that no overvoltage occurs in the inverter due to regenerative operation of the motor, and such that
the generated current does not exceed the current limit set in P 2.7.1 Output Current Limit %.
Default value:
Size Related
Parameter
342
number:
Data type:
uint32
P 5.5.4.8 Ramp 2 Type Selector
Use this parameter to select the ramp type, depending on requirements for acceleration and deceleration. A linear ramp provides
constant acceleration during ramping. Sine Ramp and Sine 2 Ramp provide non-linear acceleration.
Default value:
0 [Linear]
Danfoss A/S © 2024.03
Parameter type:
Unit:
Access type:
Selection description
Only be used with speed control mode) S-ramp based on the
values set in P 5.5.4.2 Ramp 1 Accel. Time and P 5.5.4.3 Ramp 1
Decel. Time.
Parameter type:
Unit:
Access type:
Parameter type:
Unit:
Access type:
Parameter type:
AB413939445838en-000301 / 130R1254 |
Selection
Read/Write
Range (0.01–3600.00)
s
Read/Write
Range (0.01–3600.00)
s
Read/Write
Selection
163