Danfoss iC2 Application Manual page 183

Micro frequency converters
Table of Contents

Advertisement

Application Guide | iC2-Micro Frequency Converters
Sleep mode is not active when local reference is active (set speed manually with navigation buttons on the control panel). Does
not work in Local mode. Remote setup in open loop must be carried out before setting input/output in closed loop.
P 5.12.7.1 Sleep Mode in Process Closed-loop Mode
This parameter is for sleep mode running in process closed loop. Use this parameter to set whether the feedback is detected for entering
sleep mode.
Default value:
0
Parameter
2202
number:
Data type:
enum
Selection number
Selection name
0
Feed. and Speed
1
Speed
2
Feedback
P 5.12.7.2 Minimum Run Time
Set the minimum running time for the motor after a start command (digital input or bus) before entering the sleep mode.
Default value:
10
Parameter
2240
number:
Data type:
uint16
P 5.12.7.3 Minimum Sleep Time
Set the minimum time for staying in sleep mode. This setting overrides any wake-up conditions.
Default value:
10
Parameter
2241
number:
Data type:
uint16
P 5.12.7.4 Wake-Up Speed [Hz]
This parameter is used when P 5.4.2 Operation Mode is set for open loop, and the speed reference is from an external controller. Set the
reference speed when the Sleep Mode is deactivated.
Default value:
100
Parameter
2243
number:
Danfoss A/S © 2024.03
  NOTICE
Parameter type:
Unit:
Access type:
Selection description
Feedback is detected together with the speed.
Feedback is not detected, only sleep speed and time are
checked.
Feedback is detected only.
Parameter type:
Unit:
Access type:
Parameter type:
Unit:
Access type:
Parameter type:
Unit:
Selection
Read/Write
Range (0–600)
s
Read/Write
Range (0–600)
s
Read/Write
Range (0–4000)
Hz
AB413939445838en-000301 / 130R1254 |
183