Danfoss iC2 Application Manual page 254

Micro frequency converters
Table of Contents

Advertisement

Application Guide | iC2-Micro Frequency Converters
Parameter
621
number:
Data type:
uint16
P 9.5.3.3 T34 Low Voltage
Enter the voltage (V) that corresponds to the low reference value (set in P 9.5.3.7 T34 Low Ref./Feedb. Value). The value must be set at
>1 V in order to activate the live zero timeout function in P 9.5.6.2 Live Zero Timeout Function.
Default value:
0.07
Parameter
620
number:
Data type:
uint16
P 9.5.3.4 T34 High Current
Enter the current (mA) that corresponds to the high reference value (set in P 9.5.3.6 T34 High Ref./Feedb. Value).
Default value:
20.00
Parameter
623
number:
Data type:
uint16
P 9.5.3.5 T34 Low Current
Enter the current (mA) that corresponds to the low reference value, set in P 9.5.3.7 T34 Low Ref./Feedb. Value. The value must be set at
>2 mA in order to activate the Live Zero Timeout function in P 9.5.6.2 Live Zero Timeout Function.
Default value:
4.00
Parameter
622
number:
Data type:
uint16
P 9.5.3.6 T34 High Ref./Feedb. Value
Enter the reference or feedback value that corresponds to the voltage or current set in P 9.5.3.2 T34 High Voltage or P 9.5.3.4 T34 High
Current.
Default value:
Size Related
Parameter
625
number:
Data type:
int 32
P 9.5.3.7 T34 Low Ref./Feedb. Value
Enter the reference or feedback value that corresponds to the voltage or current set in parameter P 9.5.3.3 T34 High Voltage or P 9.5.3.5
T34 High Current.
Default value:
0
254
| Danfoss A/S © 2024.03
Unit:
Access type:
Parameter type:
Unit:
Access type:
Parameter type:
Unit:
Access type:
Parameter type:
Unit:
Access type:
Parameter number:
Unit:
Access type:
Parameter number:
V
Read/Write
Range (0.00–10.00)
V
Read/Write
Range (0.00–20.00)
mA
Read/Write
Range (0.00–20.00)
mA
Read/Write
Range (-4999.000–4999.000)
Read/Write
Range (-4999.000–4999.000)
AB413939445838en-000301 / 130R1254