Application Guide | iC2-Micro Frequency Converters
Selection number
11
13
15
16
81
82
83
84
85
86
87
88
P 5.27.2 PCD Read Selection
Use this parameter to select the parameters to be assigned to the PCDs of the telegrams. The number of available PCDs depends on the
telegram type. PCDs contain the actual data values of the selected parameters.
Enter up to 16 different preset mapping 0–15 in this parameter, using array programming. If this parameter is active, addresses 2910–
2925 represent values of the 16 parameters. If this parameter is not active, addresses 2910 and 2911 are used as status word register and
main actual value. Addresses 2912–2925 are reserved.
Default value:
0 [None]
Parameter
843
number:
Data type:
enum
The following are the selections for the parameter:
Selection number
0
1
2
3
4
5
6
7
186
| Danfoss A/S © 2024.03
Selection name
Digital & Relay Bus Control
Terminal 31 Output Bus Control
FC Port CTW
FC Port REF
User Define 0
User Define 1
User Define 2
User Define 3
User Define 4
User Define 5
User Define 6
User Define 7
Parameter type:
Unit:
Access type:
Selection name
None
Operation Hours
Running Hours
kWh Counter
Control Word
Reference [Unit]
Reference %
Status Word
Selection
Read/Write
AB413939445838en-000301 / 130R1254