Danfoss iC2 Application Manual page 155

Micro frequency converters
Table of Contents

Advertisement

Application Guide | iC2-Micro Frequency Converters
Use this parameter to select whether the drive setup selection is controlled via the terminals (digital input) and/or via the fieldbus.
This parameter is active only when P 5.5.1.1 Control Place Selection is set to [0] Digital and control word.
Default value:
3 [Logic OR]
Parameter
855
number:
Data type:
enum
The following are the selections for the parameter.
Selection number
Selection name
0
Digital input
1
Bus
2
Logic AND
3
Logic OR
P 5.5.2.7 Preset Reference Select
Use this parameter to select whether the drive Preset Reference selection is controlled via the terminals (digital input) and/or via the
fieldbus.
This parameter is active only when P 5.5.1.1 Control Place Selection is set to [0] Digital and control word.
Default value:
3 [Logic OR]
Parameter
856
number:
Data type:
enum
The following are the selections for the parameter.
Selection number
Selection name
0
Digital input
1
Bus
Danfoss A/S © 2024.03
  NOTICE
Parameter type:
Unit:
Access type:
Selection description
A digital input triggers the setup selection.
A serial communication port or the fieldbus triggers the setup
selection.
The fieldbus/serial communication port and a digital input
trigger the setup selection.
The fieldbus/serial communication port or a digital input triggers
the setup selection.
  NOTICE
Parameter type:
Unit:
Access type:
Selection description
A digital input triggers the preset reference selection.
A serial communication port or the fieldbus triggers the preset
reference selection.
Selection
Read/Write
Selection
Read/Write
AB413939445838en-000301 / 130R1254 |
155