Application Guide | iC2-Micro Frequency Converters
Default value:
Size Related
Parameter
381
number:
Data type:
uint32
Speed Control (Menu Index 5.8)
7.6.7
P 5.8.1 Rotation Direction
Use this parameter to select the motor speed directions required. Use this parameter to prevent unwanted reversing.
Default value:
2 [Both directions]
Parameter
410
number:
Data type:
enum
The following are the selections for the parameter.
Selection number
Selection name
0
Clockwise
2
Both directions
P 5.8.2 Motor Speed High Limit [Hz]
Use this parameter to enter the maximum limit for motor speed. The parameter can be set to match the maximum motor speed
recommended by the manufacturer. The Motor Speed High Limit must exceed the value in P 5.8.3 Motor Speed Low Limit [Hz]. The
output frequency must not exceed 1/10 of the switching frequency.
Default value:
65.0
Parameter
414
number:
Data type:
uint16
P 5.8.3 Motor Speed Low Limit [Hz]
Use this parameter to enter the minimum limit for motor speed. The motor speed low limit can be set to correspond to the minimum
output frequency of the motor shaft. The motor speed low limit must not exceed P 5.8.2 Motor Speed High Limit.
Default value:
0.0
Parameter
412
number:
Data type:
uint16
172
| Danfoss A/S © 2024.03
Parameter type:
Unit:
Access type:
Parameter type:
Unit:
Access type:
Selection description
Only operation in clockwise direction is allowed.
Operation in both clockwise and counterclockwise directions are
allowed.
Parameter type:
Unit:
Access type:
Parameter type:
Unit:
Access type:
Range (0.01–3600.00)
s
Read/Write
Selection
Read/Write
Range (Size Related)
Hz
Read/Write
Range (Size Related)
Hz
Read/Write
AB413939445838en-000301 / 130R1254