Danfoss iC2 Application Manual page 246

Micro frequency converters
Table of Contents

Advertisement

Application Guide | iC2-Micro Frequency Converters
Parameter
507
number:
Data type:
uint16
P 9.4.4.8 T18 Low Duty
When setting variable duty cycle pulse signal as the reference, use this parameter to enter the pulse PWM input low duty (%) that
corresponds to the low reference value in P 9.4.4.4 Term. 18 Low Ref./Feedb. Value.
Default value:
0
Parameter
506
number:
Data type:
uint16
T15 as Pulse Output (Menu Index 9.4.5)
7.9.2.5
P 9.4.5.1 T15 Pulse Output Variable
Select the desired output on terminal 15.
Default value:
0
Parameter
560
number:
Data type:
enum
The following are the selections for the parameter.
Selection number
0
45
48
100
101
102
103
104
105
106
107
109
113
246
| Danfoss A/S © 2024.03
Unit:
Access type:
Parameter type:
Unit:
Access type:
Parameter type:
Unit:
Access type:
Selection name
No Operation
Bus Control
Bus Control, Timeout
Output Frequency
Reference
Process Feedback
Motor Current
Torque Relate to Limit
Torque Relate to Rated
Power
Speed
Max Out Frequency
PID Clamped Output
%
Read/Write
Range (0–9900)
%
Read/Write
Selection
Read/Write
AB413939445838en-000301 / 130R1254