Application Guide | iC2-Micro Frequency Converters
Inching (Menu Index 5.9)
7.6.8
P 5.9.1 Jog Ramp Time
Use this parameter to enter the jog ramp time, which is the acceleration/deceleration time between 0 Hz and the rated motor frequency
P 4.2.2.4 Nominal Frequency. Ensure that the resulting output current required for the given jog ramp time does not exceed the current
limit in P 2.7.1 Current Limit.
Default value:
Size Related
Parameter
380
number:
Data type:
uint32
Hz
P 5.8.2 Motor Speed
High Limit[Hz]
P 4.2.2.4 Nominal
Frequency
P 5.9.2 Jog
Reference
P 5.8.3 Motor Speed
Low Limit [Hz]
t jog
P 5.9.1 Jog
Ramp Time
(acc)
Figure 77: Jog Ramp Time
P 5.9.2 Jog Reference
Use this parameter to set the jog speed. The jog speed is a fixed output speed at which the frequency converter is running when the jog
function is activated.
Default value:
5.0
Parameter
311
number:
Data type:
uint16
Torque Control (Menu Index 5.10)
7.6.9
P 5.10.1 Motor Torque Limit
Use this parameter to enter the maximum torque limit for motor operation. This function limits the torque on the shaft to protect the
mechanical installation.
Default value:
Size Related
Parameter
416
number:
Data type:
uint16
174
| Danfoss A/S © 2024.03
t jog
Time
P 5.9.1 Jog
Ramp Time
(dec)
Parameter type:
Unit:
Access type:
Parameter type:
Unit:
Access type:
Parameter type:
Unit:
Access type:
Range (0.01–3600.00)
s
Read/Write
Range (0.0–500.0)
Hz
Read/Write
Range (Size Related)
%
Read/Write
AB413939445838en-000301 / 130R1254