Application Guide | iC2-Micro Frequency Converters
Use this parameter to select the function of the Stop/Reset button. To avoid accidental stop or reset of the drive from control panel, select
[0] Disabled. The setting can be locked by P 6.6.20 Password.
Default value:
1 [Enabled]
Parameter
44
number:
Data type:
enum
The following are the selections for the parameter.
Selection number
0
1
7
Digital/Bus (Menu Index 5.5.2)
7.6.4.2
P 5.5.2.1 Coasting Select
Use this parameter to select whether the coasting function is controlled via the terminals (digital input) and/or via the bus.
This parameter is active only when P 5.5.1.1 Control Place Selection is set to [0] Digital and control word.
Default value:
3 [Logic OR]
Parameter
850
number:
Data type:
enum
The following are the selections for the parameter.
Selection number
Selection name
0
Digital input
1
Bus
2
Logic AND
3
Logic OR
P 5.5.2.2 Quick Stop Select
Use this parameter to select whether the Quick Stop function is controlled via the terminals (digital input) and/or via the bus.
152
| Danfoss A/S © 2024.03
Parameter type:
Unit:
Access type:
Selection name
Disabled
Enabled
Reset Only Enabled
  NOTICE
Parameter type:
Unit:
Access type:
Selection description
Activate the coasting command via a digital input
Activate the coasting command via the serial communication
port or fieldbus option.
Activate the coasting command via the fieldbus/serial
communication port and 1 extra digital input.
Activate the coasting command via the fieldbus/serial
communication port or via 1 of the digital inputs.