Application Guide | iC2-Micro Frequency Converters
Selection number
0
1
P 9.3.7 T34 Analog Input
View actual input on analog input 34 (current or voltage).
Default value:
1.00
Parameter
1664
number:
Data type:
uint16
P 9.3.8 T18 Pulse Input [Hz]
View the actual value of the frequency applied at terminal 18 as an impulse input.
Default value:
0
Parameter
1668
number:
Data type:
int32
P 9.3.9 T15 Pulse Output [Hz]
View the actual value of impulses applied to terminal 15 in digital output mode.
Default value:
0
Parameter
1669
number:
Data type:
int32
P 9.3.10 Relay Output
View the state of the relay outputs. The value should be analyzed using binary type. (0=off, 1=on). From the far right to left,
corresponding to bit 4 is Relay Output 1.
Default value:
0
Parameter
1671
number:
Data type:
uint16
Digital Inputs/Outputs (Menu Index 9.4)
7.9.2
Digital Input Setting (Menu Index 9.4.1)
7.9.2.1
P 9.4.1.1 Digital I/O mode
For digital I/O: Select [0] PNP for action on positive directional pulses. PNP are pulled down to GND. Select [1] NPN systems for action on
negative directional pulses. NPN are pulled up to +24 V, inside the drive.
Danfoss A/S © 2024.03
Selection name
Current mode
Voltage mode
Parameter type:
Unit:
Access type:
Parameter type:
Unit:
Access type:
Parameter type:
Unit:
Access type:
Parameter type:
Unit:
Access type:
AB413939445838en-000301 / 130R1254 |
Range (0.00–20.00)
Read
Range (0–130000)
Read
Range (0–40000)
Read
Range (0–31)
Read
219