Filters & Brake Chopper (Menu Index 3); Status (Menu Index 3.1); Brake Chopper (Menu Index 3.2) - Danfoss iC2 Application Manual

Micro frequency converters
Table of Contents

Advertisement

Application Guide | iC2-Micro Frequency Converters
Data type:
uint16
P 2.7.5 Trip Delay at Current Limit
When the output current reaches the current limit (P 2.7.1 Output Current Limit %), a warning is triggered. If the current limit warning is
continuously present for the period specified in this parameter, the frequency converter trips. Enter 60 s = OFF to disable the feature.
Default value:
60
Parameter
1424
number:
Data type:
uint8
Filters & Brake Chopper (Menu Index 3)
7.4

Status (Menu Index 3.1)

7.4.1
P 3.1.1 Brake Energy
View the brake power transmitted to an external brake resistor. The mean power is calculated on an average basis for the most recent
120 s.
Default value:
0
Parameter
1633
number:
Data type:
uint32

Brake Chopper (Menu Index 3.2)

7.4.2
P 3.2.1 Enable Brake Chopper
Select method for dissipation of excess brake energy.
Default value:
0 [Disable]
Parameter
215
number:
Data type:
enum
Selection number
0
1
P 3.2.2 Brake Chopper Voltage Reduce
This parameter can reduce the DC voltage where the brake resistor is active. It is only valid for T4 unit.
Default value:
Size Related
Danfoss A/S © 2024.03
Access type:
Parameter type:
Unit:
Access type:
Parameter type:
Unit:
Access type:
Parameter type:
Unit:
Access type:
Selection name
Disable
Enable
Parameter type:
AB413939445838en-000301 / 130R1254 |
Read/Write
Range (0–60)
s
Read/Write
Range (0.000–10000.000)
kW
Read
Selection
Read/Write
Range (Size Related)
119