Danfoss iC2 Application Manual page 151

Micro frequency converters
Table of Contents

Advertisement

Application Guide | iC2-Micro Frequency Converters
Selection number
0
1
2
P 5.5.1.10 Operating State at Power-up
Select operating mode for restart upon reconnection of the drive to mains voltage after power down. This function is active in Local
mode only.
Default value:
1 [Forced stop, ref = old]
Parameter
4
number:
Data type:
enum
The following are the selections for the parameter.
Selection number
Selection name
0
Resume
1
Forced Stop, Ref.=old
2
Forced Stop, Ref.=0
P 5.5.1.15 [REM/LOC] Button
Use this parameter to select the function of the REM/LOC button. To avoid accidental LOC/REM change of the drive, select [0] Disabled.
The setting can be locked by P 6.6.20 Password.
Default value:
1 [Enabled]
Parameter
46
number:
Data type:
enum
The following are the selections for the parameter.
Selection number
0
1
P 5.5.1.16 [Stop/Reset] Button
Danfoss A/S © 2024.03
Selection name
None
Profile default
CTW valid, active low
Parameter type:
Unit:
Access type:
Selection description
Restart the frequency converter, maintaining the start or stop
settings using START or STOP button, selected before power-
down of the frequency converter.
Restart the frequency converter with a saved local reference after
mains voltage reappears, after pressing START.
Reset the local reference to 0 upon restarting the frequency
converter.
Parameter type:
Unit:
Access type:
Selection name
Disabled
Enabled
AB413939445838en-000301 / 130R1254 |
Selection
Read/Write
Selection
Read/Write
151