Danfoss iC2 Application Manual page 159

Micro frequency converters
Table of Contents

Advertisement

Application Guide | iC2-Micro Frequency Converters
The following are the selections for the parameter.
Selection number
Selection name
0
Sum
1
External/Preset
P 5.5.3.6 Reference Site
Use this parameter to select which reference site to activate. To use the local reference in Local mode, or the remote reference in
Remote mode, select [0] Linked to Loc / Rem. To use the same reference in both Remote and Local modes, select [1] Remote or [2] Local
respectively.
Default value:
0 [Linked to Loc/Rem]
Parameter
313
number:
Data type:
enum
The following are the selections for the parameter.
Selection number
0
1
2
P 5.5.3.7 Reference 1 Source
Use this parameter to select the input for the 1st reference signal. The parameters P 5.5.3.7 Reference 1 Source, P 5.5.3.8 Reference 2
Source, and P 5.5.3.9 Reference 3 Source define up to 3 different reference signals. The sum of these reference signals defines the actual
reference.
Default value:
1 [Analog Input 33]
Parameter
315
number:
Data type:
enum
The following are the selections for the parameter.
Selection number
0
1
2
8
Danfoss A/S © 2024.03
Selection description
Sum both external and preset reference sources.
Use either the preset or the external reference source. Shift
between external and preset via a command or a digital input.
Parameter type:
Unit:
Access type:
Selection name
Linked to Loc/Rem
Remote
Local
Parameter type:
Unit:
Access type:
Selection name
No function
Analog Input 33
Analog Input 34
Frequency Input 18
AB413939445838en-000301 / 130R1254 |
Selection
Read/Write
Selection
Read/Write
159