Grid Protection (Menu Index 1.3)

7.2.2
P 1.3.1 Mains Imbalance Action
Select an action of frequency converter on detecting a severe mains imbalance. Operation during severe mains imbalance reduces the
lifetime of the frequency converter. When selecting [4] Fast Trip or [5] Fast Warning, P 1.2.1 Regional settings must match the frequency
of actual grid to avoid false faults.
Conditions are considered severe if the motor is operated continuously near nominal load (for example, a pump or fan running near full
speed).
Default value:
0 [Trip]
Danfoss A/S © 2024.03
Selection name
200-240V/50Hz/IT-grid
200-240V/50Hz/Delta
200-240V/50Hz
100-110V/50Hz/IT-grid
100-110V/50Hz/Delta
100-110V/50Hz
380-440V/50Hz/IT-grid
380-440V/50Hz/Delta
380-440V/50Hz
440-480V/50Hz/IT-grid
440-480V/50Hz/Delta
440-480V/50Hz
200-240V/60Hz/IT-grid
200-240V/60Hz/Delta
200-240V/60Hz
100-110V/60Hz/IT-grid
100-110V/60Hz/Delta
100-110V/60Hz
380-440V/60Hz/IT-grid
380-440V/60Hz/Delta
380-440V/60Hz
440-480V/60Hz/IT-grid
440-480V/60Hz/Delta
440-480V/60Hz
Parameter type: