Danfoss iC2 Application Manual page 149

Micro frequency converters
Table of Contents

Advertisement

Application Guide | iC2-Micro Frequency Converters
Parameter
101
number:
Data type:
enum
The following are the selections for the parameter.
Selection number
Selection name
0
U/f
1
VVC+
When P 4.2.1.1 Motor Type is set to PM enabled options, only VVC+ option is available.
Control (Menu Index 5.5)
7.6.4
General Settings (Menu Index 5.5.1)
7.6.4.1
P 5.5.1.1 Control Place Selection
Use this parameter to select the control place of the unit.
Default value:
0 [Digital and Ctrl. word]
Parameter
801
number:
Data type:
enum
The following are the selections for the parameter.
Selection number
Selection name
0
Digital and Ctrl. word
1
Digital only
2
Control word only
P 5.5.1.2 Control Source
Use this parameter to select the source of the control word.
Default value:
1 [FC Port]
Parameter
802
number:
Data type:
enum
The following are the selections for the parameter.
Danfoss A/S © 2024.03
Unit:
Access type:
Selection description
When running U/f, control slip and load compensations are not
included. The control is used for parallel-connected motors and/
or special motor applications
Normal running mode, including slip and load compensations.
  NOTICE
Parameter type:
Unit:
Access type:
Selection description
Use both the digital input and the control word.
Use the digital input only.
Use the control word only.
Parameter type:
Unit:
Access type:
Read/Write
Selection
Read/Write
Selection
Read/Write
AB413939445838en-000301 / 130R1254 |
149

Advertisement

Table of Contents
loading

Table of Contents