Parameter
No.
Pn001
Function Selection Application Switches 1
2nd
3rd
4th
digit
digit
digit
n.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Name
Setting Range
1st
digit
Servo OFF or Alarm Stop Mode
(Refer to "8.3.5 Selecting the Stopping Method After Servo OFF.")
0
Stops the motor by applying dynamic brake (DB).
1
Stops the motor by applying dynamic brake (DB) and then releases DB.
2
Makes the motor coast to a stop state without using the dynamic brake (DB).
Overtravel (OT) Stop Mode
(Refer to "8.3.3 Setting the Overtravel Limit Function.")
0
Same setting as Pn001.0 (Stops the motor by applying DB or by coasting).
1
Sets the torque of Pn406 to the maximum value, decelerate the motor to a stop, and then sets it
to servolock state.
Sets the torque of Pn406 to the maximum value, decelerates the motor to a stop, and then sets it
2
to coasting state.
AC/DC Power Input Selection
(Refer to "6.1.3 Typical Main Circuit Wirning Examples.")
Not applicable to main circuit DC power input: Input AC power supply through L1, L2 (, and L3)
0
terminals.
Applicable to main circuit DC power input: Input DC power supply between + 1 and
1
Warning Code Output Selection
(Refer to "11.1.2 Warning Display.")
ALO1, ALO2, and ALO3 output only alarm codes.
0
1
ALO1, ALO2, and ALO3 output both alarm codes and warning codes. While warning
codes are output, ALM signal output remains ON (normal state).
Factory
Units
Setting
−
−
0000
12.3 List of Parameters
Setting
Reference
Validation
Section
−
After
restart
12
12-27
Need help?
Do you have a question about the SGM H Series and is the answer not in the manual?