Item
Set the network No. of the GOT.
GOT NET No.
<Default: 1>
Set the station No. of the GOT.
GOT PC No.
<Default: 1>
Set the IP address of the GOT.
GOT IP Address
<Default: 192.168.0.18>
GOT Port No.
Set the GOT port No. for the connection with the Ethernet module.
*1
<Default: 5001>
(QJ71E71/AJ71(Q)E71)
GOT Port No.
Set the GOT port No. for Ethernet download.
(Ethernet Download)
<Default: 5014>
Set the router address of the default gateway where the GOT is
Default Gateway
connected. (Only for communication via router)
<Default: 0.0.0.0>
Set the subnet mask for the sub network. (Only for connection via
router)
Subnet Mask
If the sub network is not used, the default value is set.
<Default: 255.255.255.0>
Set the number of retries to be performed when a communication
error occurs.
Retry
When receiving no response after retries, the communication
times out.
<Default: 3 Times>
Specify the time period from the GOT startup until GOT starts the
Startup Time
communication with the PLC CPU.
<Default: 3 Sec>
Set the time period for a communication to time out.
*2*3
Timeout Time
<Default: 3 Sec>
Set the delay time for reducing the load of the network/destination
*4
PLC.
Delay Time
<Default: 0ms>
*1
No setting is required for "Gateway" of the communication details setting.
*2
When using the mail send function:
Specify the "Timeout Time" after connection to the SMTP server. (However, the communication timeout time of
about one minute is fixed for the case where connection with the SMTP server is failed after starting mail
transmission.)
*3
To connect the GOT with the Ethernet module (Q Series) in the one-on-one relationship using a cross cable, set
[Timeout Time] to 6 sec. or longer.
*4
When using the mail send function:
Specify the time of transmission interval between one mail and the next mail when sending multiple mails.
Description
31.2 Preparatory Procedures for Monitoring
31.2.3 Setting communication interface (Communication settings)
Range
1 to 239
1 to 64
0.0.0.0 to 255.255.255.255
1024 to 5010, 5014 to 65534
(Except for 5011, 5012 and 5013)
1024 to 5010, 5014 to 65534
(Except for 5011, 5012 and 5013)
0.0.0.0 to 255.255.255.255
0.0.0.0 to 255.255.255.255
0 to 5 Times
3 to 255 Sec
3 to 90 Sec
0 to 10000 ( 10 ms)
31 - 11
25
26
27
28
29
30
31

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents