Stw1 Control Word Interconnection - Siemens SINAMICS G120 Manual

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Signal targets for fieldbus STW1 (p0700 = 6)
Signal
Meaning
= ON (pulses can be enabled)
STW1.0
0 = OFF1 (braking with ramp-function generator, then pulse cancellation & ready for switching on)
1 = No OFF2 (enable is possible)
STW1.1
0 = OFF2 (immediate pulse suppression and switching on inhibited)
1 = No OFF3 (enable is possible)
STW1.2
0 = OFF3 (braking with the OFF3 ramp p1135, then pulse suppression and switching on inhibited)
1 = Enable operation (pulses can be enabled)
STW1.3
0 = Inhibit operation (cancel pulses)
1 = Operating condition (the ramp-function generator can be enabled)
STW1.4
0 = Inhibit ramp-function generator (set the ramp-function generator output to zero)
1 = Enable the ramp-function generator
STW1.5
0 = Stop the ramp-function generator (freeze the ramp-function generator output)
1 = Enable setpoint
STW1.6
0 = Inhibit setpoint (set the ramp-function generator input to zero)
STW1.7
= Acknowledge faults
STW1.8
Reserved
STW1.9
Reserved
STW1.10
1 = Control via PLC
STW1.11
1 = Dir of rot reversal
STW1.12
Reserved
STW1.13
1 = Motorized potentiometer, setpoint, raise
STW1.14
1 = Motorized potentiometer, setpoint, lower
STW1.15
Reserved
<1>
Bit 10 in STW1 must be set to ensure that the drive accepts the process data.
1
2
Fieldbus Interface (USS, Modbus, BACnet on RS485)

STW1 control word interconnection

<1>
3
4
[Function diagram]
[Function diagram]
Interconnection
internal control word
parameters
p0840[0] = r2090.0
[2501.3]
Sequence control
p0844[0] = r2090.1
[2501.3]
Sequence control
p0848[0] = r2090.2
[2501.3]
Sequence control
Sequence control
p0852[0] = r2090.3
[2501.3]
p1140[0] = r2090.4
[2501.3]
[3060] [3070] [3080]
p1141[0] = r2090.5
[2501.3]
p1142[0] = r2090.6
[2501.3]
[3060] [3070] [3080]
p2103[0] = r2090.7
[2546.1]
-
-
-
-
p0854[0] = r2090.10
[2501.3]
p1113[0] = r2090.11
[2505.3]
-
-
p1035[0] = r2090.13
[2505.3]
p1036[0] = r2090.14
[2505.3]
-
-
5
6
Function diagram
FP_9342_97_62.vsd
G120 CU230P-2 HVAC
13.12.2010
V4.4
Inverted
signal target
-
-
-
-
-
[3060] [3070]
-
-
[8060]
-
-
-
-
-
[2501]
-
[3040]
-
-
-
[3020]
-
[3020]
-
-
-
7
8
- 9342 -