Siemens SINAMICS G120 Manual page 382

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Parameters
List of Parameters
p11074
Free tec_ctrl 0 differentiation time constant / Ftec0 D comp T
Access level: 2
Can be changed: U, T
Units group: -
Min
0.000 [s]
Description:
Sets the time constant for the differentiation (D component) of the free technology controller 0.
Note:
Value = 0: Differentiation is de-activated.
p11080
Free tec_ctrl 0 proportional gain / Ftec0 Kp
Access level: 2
Can be changed: U, T
Units group: -
Min
0.000
Description:
Sets the proportional gain (P component) of the free technology controller 0.
Note:
Value = 0: The proportional gain is de-activated.
p11085
Free tec_ctrl 0 integral time / Ftec0 Tn
Access level: 2
Can be changed: U, T
Units group: -
Min
0.000 [s]
Description:
Sets the integral time (I component, integrating time constant) of the free technology controller 0.
Note:
Value = 0: The integral time is disabled.
If the parameter is set to zero during operation, the I component retains its most recent value.
p11091
CO: Free tec_ctrl 0 limit maximum / Ftec0 lim max
Access level: 3
Can be changed: U, T
Units group: -
Min
-200.00 [%]
Description:
Sets the maximum limit of the free technology controller 0.
Dependency:
Refer to: p11092
Note:
The maximum limit must always be greater than the minimum limit (p11091 > p11092).
p11092
CO: Free tec_ctrl 0 limit minimum / Ftec0 lim min
Access level: 3
Can be changed: U, T
Units group: -
Min
-200.00 [%]
Description:
Sets the minimum limit of the free technology controller 0.
Dependency:
Refer to: p11091
Note:
The maximum limit must always be greater than the minimum limit (p11091 > p11092).
1-382
Calculated: -
Scaling: -
Unit selection: -
Max
60.000 [s]
Calculated: -
Scaling: -
Unit selection: -
Max
1000.000
Calculated: -
Scaling: -
Unit selection: -
Max
10000.000 [s]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
200.00 [%]
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
200.00 [%]
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Data type: FloatingPoint32
Data set: -
Factory setting
0.000 [s]
Data type: FloatingPoint32
Data set: -
Factory setting
1.000
Data type: FloatingPoint32
Data set: -
Factory setting
30.000 [s]
Data type: FloatingPoint32
Data set: -
Factory setting
100.00 [%]
Data type: FloatingPoint32
Data set: -
Factory setting
0.00 [%]
© Siemens AG 2011 All Rights Reserved

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu230p-2

Table of Contents