Siemens SINAMICS G120 Manual page 115

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

r0945[0...63]
Fault code / Fault code
Access level: 3
Can be changed: -
Units group: -
Min
-
Description:
Displays the numbers of faults that have occurred.
Dependency:
Refer to: r0947, r0948, r0949, r2109, r2130, r2133, r2136
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
Fault buffer structure (general principle):
r0945[0], r0949[0], r0948[0], r2109[0] --> actual fault case, fault 1
. . .
r0945[7], r0949[7], r0948[7], r2109[7] --> actual fault case, fault 8
r0945[8], r0949[8], r0948[8], r2109[8] --> 1st acknowledged fault case, fault 1
. . .
r0945[15], r0949[15], r0948[15], r2109[15] --> 1st acknowledged fault case, fault 8
. . .
r0945[56], r0949[56], r0948[56], r2109[56] --> 7th acknowledged fault case, fault 1
. . .
r0945[63], r0949[63], r0948[63], r2109[63] --> 7th acknowledged fault case, fault 8
r0946[0...65534] Fault code list / Fault code list
Access level: 3
Can be changed: -
Units group: -
Min
-
Description:
Lists the fault codes stored in the drive unit.
The indices can only be accessed with a valid fault code.
Dependency:
The parameter assigned to the fault code is entered in r0951 under the same index.
r0947[0...63]
Fault number / Fault number
Access level: 2
Can be changed: -
Units group: -
Min
-
Description:
This parameter is identical to r0945.
r0948[0...63]
Fault time received in milliseconds / t_fault recv ms
Access level: 3
Can be changed: -
Units group: -
Min
- [ms]
Description:
Displays the system runtime in milliseconds when the fault occurred.
Dependency:
Refer to: r0945, r0947, r0949, r2109, r2130, r2133, r2136, p8400
Notice:
The time comprises r2130 (days) and r0948 (milliseconds).
Note:
The buffer parameters are cyclically updated in the background (refer to status signal in r2139).
The structure of the fault buffer and the assignment of the indices is shown in r0945.
When the parameter is read via PROFIdrive, the TimeDifference data type applies.
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
- [ms]
Parameters
List of Parameters
Data type: Unsigned16
Data set: -
Factory setting
-
Data type: Unsigned16
Data set: -
Factory setting
-
Data type: Unsigned16
Data set: -
Factory setting
-
Data type: Unsigned32
Data set: -
Factory setting
- [ms]
1-115

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu230p-2

Table of Contents