p20121
DIV 0 run-time group / DIV 0 RTG
Access level: 3
Can be changed: T
Units group: -
Min
5
Description:
Setting parameter for the run-time group in which instance DIV 0 of the divider is to be called.
Value:
5:
6:
9999: Do not calculate
p20122
DIV 0 run sequence / DIV 0 RunSeq
Access level: 3
Can be changed: T
Units group: -
Min
0
Description:
Setting parameter for the run sequence of instance DIV 0 within the run-time group set in p20121.
Note:
The function blocks with a lower run sequence value are calculated before function blocks with a higher run
sequence value.
p20123[0...1]
CI: DIV 1 inputs / DIV 1 inputs
Access level: 3
Can be changed: T
Units group: -
Min
-
Description:
Sets the signal source of dividend X1 and divisor X2 of instance DIV 1 of the divider.
Index:
[0] = Dividend X0
[1] = Divisor X1
r20124[0...2]
CO: DIV 1 quotient / DIV 1 quotient
Access level: 3
Can be changed: -
Units group: -
Min
-
Description:
Display parameter for quotients Y = X1/X2, integer number quotients YIN, and division remainder MOD = (Y - YIN)
x X2 of instance DIV 1 of the divider.
Index:
[0] = Quotient Y
[1] = Integer number quotient YIN
[2] = Div remainder MOD
r20125
BO: DIV 1 divisor is zero QF / DIV 1 divisor=0 QF
Access level: 3
Can be changed: -
Units group: -
Min
-
Description:
Display parameter for the signal QF that the divisor X2 of instance DIV 1 of the divider is zero.
X2 = 0.0 => QF = 1
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Run-time group 5
Run-time group 6
Calculated: -
Scaling: -
Unit selection: -
Max
9999
Calculated: -
Scaling: -
Unit selection: -
Max
32000
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
Calculated: -
Scaling: PERCENT
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Parameters
List of Parameters
Data type: Integer16
Data set: -
Factory setting
9999
Data type: Unsigned16
Data set: -
Factory setting
300
Data type: U32 / FloatingPoint32
Data set: -
Factory setting
0
Data type: FloatingPoint32
Data set: -
Factory setting
-
Data type: Unsigned32
Data set: -
Factory setting
-
1-417