p8725[0...4]
CAN Transmit PDO 6 / Transmit PDO 6
CU230P-2 CAN
Access level: 3
Can be changed: C(3), T
Units group: -
Min
0000 hex
Description:
Sets the communication parameters for CANopen Transmit Process Data Object 6 (TPDO 6).
Index:
[0] = PDO COB-ID
[1] = PDO transmission type
[2] = Inhibit time (in 100 µs)
[3] = Reserved
[4] = Event timer (in ms)
Dependency:
A valid COB-ID can only be set for the available (existing) channel.
Refer to: p8741
Notice:
For inhibit time and even timer, the following apply:
A value that is not a multiple integer of CANopen (4 ms) is rounded-off.
Note:
Corresponds to the CANopen object 1805 hex + 40 hex * x (x: Drive number 0 ... 7).
Transmission types 0, 1 ... F0, FE and FF can be set.
PDO: Process Data Object
p8726[0...4]
CAN Transmit PDO 7 / Transmit PDO 7
CU230P-2 CAN
Access level: 3
Can be changed: C(3), T
Units group: -
Min
0000 hex
Description:
Sets the communication parameters for CANopen Transmit Process Data Object 7 (TPDO 7).
Index:
[0] = PDO COB-ID
[1] = PDO transmission type
[2] = Inhibit time (in 100 µs)
[3] = Reserved
[4] = Event timer (in ms)
Dependency:
A valid COB-ID can only be set for the available (existing) channel.
Refer to: p8741
Notice:
For inhibit time and even timer, the following apply:
A value that is not a multiple integer of CANopen (4 ms) is rounded-off.
Note:
Corresponds to the CANopen object 1806 hex + 40 hex * x (x: Drive number 0 ... 7).
Transmission types 0, 1 ... F0, FE and FF can be set.
PDO: Process Data Object
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Calculated: -
Scaling: -
Unit selection: -
Max
C000 06DF hex
Calculated: -
Scaling: -
Unit selection: -
Max
C000 06DF hex
Parameters
List of Parameters
Data type: Unsigned32
Data set: -
Factory setting
[0] C000 06DF hex
[1] 00FE hex
[2] 0000 hex
[3] 0000 hex
[4] 0000 hex
Data type: Unsigned32
Data set: -
Factory setting
[0] C000 06DF hex
[1] 00FE hex
[2] 0000 hex
[3] 0000 hex
[4] 0000 hex