p2155[0...n]
Speed threshold 2 / n_thresh val 2
Access level: 3
Can be changed: U, T
Units group: 3_1
Min
0.00 [rpm]
Description:
Sets the speed threshold value for the following messages:
"|n_act| < = speed threshold value 2" (BO: r2197.1)
"|n_act| > speed threshold value 2" (BO: r2197.2)
Dependency:
Refer to: p2140, r2197
p2156[0...n]
On delay, comparison value reached / t_on cmpr val rchd
Access level: 3
Can be changed: U, T
Units group: -
Min
0.0 [ms]
Description:
Sets the switch-in delay time for the signal "comparison value reached" (BO: r2199.1).
Dependency:
Refer to: p2141, p2142, r2199
p2157[0...n]
Speed threshold 5 / n_thresh val 5
Access level: 3
Can be changed: U, T
Units group: 3_1
Min
0.00 [rpm]
Description:
Sets the speed threshold value for the following messages:
"|n_act| < = speed threshold value 5" (BO: r2198.0)
"|n_act| > speed threshold value 5" (BO: r2198.1)
Dependency:
Refer to: p2150, p2158
p2158[0...n]
Delay for n_act comparison with speed threshold value 5 / Del compar n_5
Access level: 3
Can be changed: U, T
Units group: -
Min
0 [ms]
Description:
Delay time for the comparison of the speed with the speed threshold value 5 (P2157).
Dependency:
Refer to: p2150, p2157
p2159[0...n]
Speed threshold 6 / n_thresh val 6
Access level: 3
Can be changed: U, T
Units group: 3_1
Min
0.00 [rpm]
Description:
Sets the speed threshold value for the following messages:
"|n_act| < = speed threshold value 6" (BO: r2198.2)
"|n_act| > speed threshold value 6" (BO: r2198.3)
Dependency:
Refer to: p2150, p2160
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: p0505
Max
210000.00 [rpm]
Calculated: -
Scaling: -
Unit selection: -
Max
10000.0 [ms]
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: p0505
Max
210000.00 [rpm]
Calculated: -
Scaling: -
Unit selection: -
Max
10000 [ms]
Calculated: p0340 = 1,3,5
Scaling: -
Unit selection: p0505
Max
210000.00 [rpm]
Parameters
List of Parameters
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
900.00 [rpm]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
0.0 [ms]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
900.00 [rpm]
Data type: Unsigned16
Data set: DDS, p0180
Factory setting
10 [ms]
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
900.00 [rpm]