Parameters
List of Parameters
p1260
Bypass configuration / Bypass config
Access level: 2
Can be changed: T
Units group: -
Min
0
Description:
Sets the configuration for the bypass function.
Value:
0:
3:
Note:
When the converter is switched on, the state of the bypass contactor is evaluated. If the automatic restart is active
(p1210 = 4) and both an ON command (r0054.0 = 1) and the bypass signal (p1266 = 1, configuration p1267.0 = 1)
are still present during power-up, the converter goes into "ready for operation and bypass" state (r0899.0 = 1 and
r0046.25 = 1) after power-up, and the motor continues to run directly on the line.
The "bypass" function can only be switched off again (p1260 = 0) if the bypass is not active or the bypass function
has a fault.
The flying restart function must be activated (p1200).
r1261.0...7
CO/BO: Bypass control/status word / Bypass STW / ZSW
Access level: 2
Can be changed: -
Units group: -
Min
-
Description:
Control and feedback signals of the bypass switch.
Bit field:
Bit
Signal name
00
Command switch motor - drive
01
Command switch motor - line supply
05
Feedback signal switch motor - drive
06
Feedback signal switch motor - line supply
07
Bypass command (from p1266)
Note:
Control bits 0 and 1 should be interconnected to the signal outputs via which the switches in the motor feeder
cables should be controlled. These should be selected/dimensioned for switching under load.
p1262[0...n]
Bypass dead time / Bypass t_dead
Access level: 2
Can be changed: U, T
Units group: -
Min
0.000 [s]
Description:
Sets the dead time for non-synchronized bypass.
Note:
This parameter is used to define the changeover time of the contactors. It should not be shorter than the de-magne-
tizing time of the motor (p0347).
The total changeover time for the bypass is based on the total of p1262 plus the OFF time for the relevant switch
(p1274[x]).
p1263
Debypass delay time / Debypass t_del
Access level: 2
Can be changed: U, T
Units group: -
Min
0.000 [s]
Description:
Sets the delay time to switch back to converter operation for a non-synchronized bypass.
1-172
Bypass de-activated
Bypass without synchronization
Calculated: -
Scaling: -
Unit selection: -
Max
3
Calculated: -
Scaling: -
Unit selection: -
Max
-
1 signal
Close
Close
Closed
Closed
Yes
Calculated: p0340 = 1,3
Scaling: -
Unit selection: -
Max
20.000 [s]
Calculated: -
Scaling: -
Unit selection: -
Max
300.000 [s]
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Data type: Integer16
Data set: -
Factory setting
0
Data type: Unsigned32
Data set: -
Factory setting
-
0 signal
Open
Open
Opened
Opened
No
Data type: FloatingPoint32
Data set: DDS, p0180
Factory setting
1.000 [s]
Data type: FloatingPoint32
Data set: -
Factory setting
1.000 [s]