Siemens SINAMICS G120 Manual page 109

Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

p0848[0...n]
BI: No Quick Stop / Quick Stop (OFF3) signal source 1 / OFF3 S_src 1
CU230P-2 CAN
Access level: 3
CU230P-2 HVAC
Can be changed: T
Units group: -
Min
-
Description:
Sets the first signal source for the command "No quick stop/quick stop (OFF3)".
The following signals are AND'ed:
- BI: p0848 "No quick stop / quick stop (OFF3) signal source 1"
- BI: p0849 "No quick stop / quick stop (OFF3) signal source 2"
For the PROFIdrive profile, the result of the AND logic operation corresponds to control word 1 bit 2 (STW1.2).
BI: p0848 = 0 signal or BI: p0849 = 0 signal
- OFF3 (braking along the OFF3 ramp (p1135), then pulse suppression and switch on inhibit)
BI: p0848 = 1 signal and BI: p0849 = 1 signal
- No OFF3 (enable is possible)
Caution:
When "master control from PC" is activated, this binector input is ineffective.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p0848[0...n]
BI: No Quick Stop / Quick Stop (OFF3) signal source 1 / OFF3 S_src 1
CU230P-2 DP
Access level: 3
Can be changed: T
Units group: -
Min
-
Description:
Sets the first signal source for the command "No quick stop/quick stop (OFF3)".
The following signals are AND'ed:
- BI: p0848 "No quick stop / quick stop (OFF3) signal source 1"
- BI: p0849 "No quick stop / quick stop (OFF3) signal source 2"
For the PROFIdrive profile, the result of the AND logic operation corresponds to control word 1 bit 2 (STW1.2).
BI: p0848 = 0 signal or BI: p0849 = 0 signal
- OFF3 (braking along the OFF3 ramp (p1135), then pulse suppression and switch on inhibit)
BI: p0848 = 1 signal and BI: p0849 = 1 signal
- No OFF3 (enable is possible)
Caution:
When "master control from PC" is activated, this binector input is ineffective.
Notice:
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
© Siemens AG 2011 All Rights Reserved
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Calculated: -
Scaling: -
Unit selection: -
Max
-
Calculated: -
Scaling: -
Unit selection: -
Max
-
Parameters
List of Parameters
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
1
Data type: U32 / Binary
Data set: CDS, p0170
Factory setting
[0] 2090.2
[1] 1
[2] 2090.2
[3] 2090.2
1-109

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu230p-2

Table of Contents