Parameters
List of Parameters
r0623
Stator resistance of Rs identification after powering up again / R_Stator Reset_Id
Access level: 4
Can be changed: -
Units group: -
Min
- [ohm]
Description:
Displays the identified stator resistance after the Rs identification after powering up again.
Dependency:
Refer to: p0621, p0622
p0625[0...n]
Motor ambient temperature / Mot T_ambient
Access level: 3
Can be changed: C(3), U, T
Units group: 21_1
Min
-40 [°C]
Description:
Defines the ambient temperature of the motor for calculating the motor temperature model.
Note:
The parameters for stator and rotor resistance (p0350, p0354) refer to this temperature.
If the thermal I2t motor model is activated for permanent-magnet synchronous motors (refer to p0611), p0625 is
included in the model calculation if a temperature sensor is not being used (see p0601).
p0626[0...n]
Motor overtemperature, stator core / Mot T_over core
Access level: 4
Can be changed: C(3), U, T
Units group: 21_2
Min
20 [K]
Description:
Defines the rated overtemperature of the stator core referred to the ambient temperature.
Dependency:
For 1LA7 motors (refer to p0300), the parameter is pre-set as a function of p0307 and p0311.
Refer to: p0625
Note:
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (refer to p0300).
p0627[0...n]
Motor overtemperature, stator winding / Mot T_over stator
Access level: 4
Can be changed: C(3), U, T
Units group: 21_2
Min
20 [K]
Description:
Defines the rated overtemperature of the stator winding referred to the ambient temperature.
Dependency:
For 1LA7 motors (refer to p0300), the parameter is pre-set as a function of p0307 and p0311.
Refer to: p0625
Note:
When quick commissioning is exited with p3900 > 0, then the parameter is reset if a catalog motor has not been
selected (refer to p0300).
1-80
Calculated: -
Scaling: -
Unit selection: -
Max
- [ohm]
Calculated: p0340 = 1,2
Scaling: -
Unit selection: p0505
Max
80 [°C]
Calculated: -
Scaling: -
Unit selection: p0505
Max
200 [K]
Calculated: -
Scaling: -
Unit selection: p0505
Max
200 [K]
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Data type: FloatingPoint32
Data set: -
Factory setting
- [ohm]
Data type: FloatingPoint32
Data set: MDS
Factory setting
20 [°C]
Data type: FloatingPoint32
Data set: MDS
Factory setting
50 [K]
Data type: FloatingPoint32
Data set: MDS
Factory setting
80 [K]