p8606
CAN Producer Heartbeat Time / Prod Heartb Time
CU230P-2 CAN
Access level: 3
Can be changed: T
Units group: -
Min
0 [ms]
Description:
Sets the time [ms] to cyclically send heartbeat telegrams.
The smallest cycle time is 100 ms.
When a 0 is written, then heartbeat telegrams are not sent.
Dependency:
Only adjustable if guard time = 0 (node guarding disabled).
Refer to: p8604
Note:
Corresponds to the CANopen object 1017 hex.
Either node guarding or heartbeat can be used.
r8607[0...3]
CAN Identity Object / Identity object
CU230P-2 CAN
Access level: 3
Can be changed: -
Units group: -
Min
-
Description:
General device information display.
Index:
[0] = Vendor ID
[1] = Product code
[2] = Revision number
[3] = Serial number
Note:
Corresponds to the CANopen object 1018 hex.
Re index 3:
The SINAMICS serial number comprises 60 bits. Of these bits, the following are displayed in this index:
Bits 0 ... 19: Consecutive number
Bits 20 ... 23: Production ID
- 0 hex: Development
- 1 hex: P1 unique number
- 2 hex: P2 unique number
- 3 hex: WA unique number
- 9 hex: Pattern
- F hex: All others
Bits 24 ... 27: Month of manufacture (0 means January, B means December)
Bits 28 ... 31: Year of manufacture (0 means 2002)
1-348
Calculated: -
Scaling: -
Unit selection: -
Max
65535 [ms]
Calculated: -
Scaling: -
Unit selection: -
Max
-
SINAMICS G120 Control Units CU230P-2 Parameter Manual (LH9), 01/2011
Data type: Unsigned16
Data set: -
Factory setting
0 [ms]
Data type: Unsigned32
Data set: -
Factory setting
-
© Siemens AG 2011 All Rights Reserved

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cu230p-2

Table of Contents